Data Center Electrical Calculator
HV & LV Cable Sizing Calculator (Busduct and Earth Conductor)
Free HV (HT) and LV cable sizing calculator, plus busduct and earth cable size calculation. Four IEC/IS-aligned tools in one place, each checking ampacity, voltage drop and short-circuit withstand rather than giving a rough estimate.
Conductor Sizing
Four independent engineering sizing tools — HT cables, LV cables, busducts and earthing conductors — each performing real IEC/IS-aligned calculations rather than a rough estimate.
Design Inputs
Results
Demand Load
200.00 kW
Design Current
309.16 A
Final Recommended Cable Size
120 mm²
Current Carrying Capacity
346.00 A
Size for the Load
120 mm²
Size for Short-Circuit
25 mm²
Governing Criterion
Ampacity
Utilization
89.4%
Voltage Drop
1.31%
Recommended Breaker
315 A
Protective Device Compatibility
Ib ≤ In ≤ Iz OK
Short Circuit Check
19.8 mm² req.
PASS
Calculation Formulas & Methodology
- Demand Load (kW) = Connected Load × Diversity Factor
- Design Current (A) = (Demand Load × 1000) ÷ (V × PF) for 1φ, or ÷ (√3 × V × PF) for 3φ
- Current Carrying Capacity Iz (A) = Base Ampacity × Ambient Factor × Grouping Factor × Material Factor × Installation Factor × Formation Factor
- Final Recommended Cable Size = smallest standard size that satisfies ampacity (Iz ≥ Ib), breaker coordination (In ≤ Iz), the voltage-drop limit and the short-circuit minimum cross-section together; the largest of those four minimums governs
- Voltage Drop (%) = [k × I × L × (R·cosφ + X·sinφ)] ÷ V × 100 (k = 2 for 1φ, √3 for 3φ)
- Short-Circuit Minimum Cross-Section (mm²) = √(fault energy) ÷ K (IEC 60364), with fault energy = breaker let-through I²t when entered, otherwise (Fault Current)² × Fault Duration
- Protective Device Compatibility: Ib (design current) ≤ In (breaker rating) ≤ Iz (cable capacity)
Indicative preliminary sizing tool aligned in principle with IEC 60364-5-52/5-54 and IS 732/IS 1255. Verify against manufacturer cable data sheets and the applicable local wiring regulation before final design.
Explore more calculators
Transformer Sizing
Size a power transformer to the nearest standard IEC 60076 kVA rating from connected load, power factor and spare capacity, with primary and secondary full-load current.
UPS Selection
Size a UPS system across Single, N, N+1, Distributed, 2N and 2(N+1) redundancy philosophies, with losses, battery charging load, and standard kVA rating libraries.
Generator (DG) Sizing
Size a standby diesel generator set per ISO 8528, sized on the larger of steady-state running load and the voltage-dip-limited starting requirement of the largest motor.
Breaker Sizing
Calculate full load current and recommended breaker rating for general distribution and motor feeder circuits, with instantaneous trip range for common starting methods.