Data Center Electrical Calculator

Diesel Generator (DG) Sizing Calculator

Size a standby diesel generator set per ISO 8528, sized on the larger of steady-state running load and the voltage-dip-limited starting requirement of the largest motor.

Design Inputs
Results
Running Load
800.00 kVA
Starting Requirement
940.63 kVA
Recommended Generator Set
1000 kVA
Per ISO 8528. Sized on the larger of steady-state running load and the voltage-dip-limited starting requirement of the largest motor. Verify against the alternator's transient reactance and site altitude/temperature derating with the manufacturer.